Anti-drone protection of a hospital oxygen tank — drone detection, masking net and cylinder supply sources
2026-11-13 · Małgorzata Dopierała, Damian Czyczyro, Przemysław Kostera
In brief. A vertical liquid oxygen tank next to a hospital looks from the air like a gas or fuel tank, so a drone that recognises targets from images may treat it the same way. Protection combines drone detection that alerts security and the authorities, an anti-drone net that also masks the tank, and cylinder supply sources. If the tank is damaged, the installation should switch to them automatically, and the cylinders should stand far enough away not to be destroyed by the same event.
A liquid oxygen tank supplies the medical oxygen installation of the whole hospital, from the intensive care unit to the operating theatre and the emergency department. For years it was protected against theft, vandalism and vehicle impact. Small unmanned aerial vehicles (UAVs), that is drones, have now been added to that list.
Why might a drone take an oxygen tank for a target?
A LOX tank is a stationary cryogenic tank with an ambient vaporiser and fittings. It stands outdoors, usually next to the hospital building, and is clearly visible from the air and in publicly available satellite images. Its location is easy to establish.
A drone does not need an operator who sees the target up close. It may be controlled from a long distance over the LTE mobile network or programmed to recognise objects in images on its own, striking whatever resembles the patterns in its database. If that database contains gas or fuel tanks, a vertical cylindrical oxygen tank resembles them by its very design. Oxygen tanks at hospitals are therefore exposed to situations similar to those of fuel tanks, and masking makes the tank harder to recognise in both cases.
Oxygen does not burn by itself, but it strongly supports combustion. Damaged fittings, a damaged vaporiser or pipeline near an ignition source can cause a fire that is difficult to control. An interruption of the oxygen supply also affects all wards at the same time.
The guide “Medical gases in practice. Volume 1” (GMWP), prepared by INMED S.A., treats the liquid oxygen tank as part of the hospital’s critical infrastructure. Damage to it can limit the hospital’s ability to provide care and, during a crisis, disaster or armed conflict, affect the protection of the population.
What does protecting an oxygen tank against drones consist of?
One device is not enough, because each element addresses a different situation.
| Element | Task | Solution |
|---|---|---|
| detection | spot a drone near the tank and alert security and the authorities | passive RF drone detection system |
| cover and masking | stop a drone or a dropped payload and make the tank harder to recognise from the air | anti-drone net on a lightweight structure, camouflage matched to the surroundings |
| continuity of supply | keep oxygen in the installation when the tank is damaged | automatic switchover to cylinder supply sources placed at a safe distance |
A net without detection gives security neither time to react nor the information that someone was observing the tank. Detection alone only reports that a drone is near the tank. Neither will keep the supply going if the tank is hit despite everything.
Why does a hospital need drone detection if it cannot shoot drones down?
People associate drone detection with neutralisation, but at a hospital its main job is to inform. A drone circling over an oxygen tank may be carrying out surveillance, and the hospital does not know whether it is being filmed by a private person who will later upload the video to YouTube or by a foreign intelligence service. Every such flight should therefore be recorded and passed on to security and from there to the relevant authorities.
A passive RF detection system listens for the signals a drone uses to communicate with its operator: control, video and telemetry. It identifies the drone type and the direction it is coming from. Newer systems also read the identifiers broadcast by drones (Remote ID) and often show the operator’s position. The system emits nothing, so the operator does not know they have been spotted, and the hospital’s radio equipment works without interference.
Requirements for an RF drone detection system
- Range matched to the site. For a single tank a few hundred metres is usually enough, and public tenders sometimes require at least 500 m around the tank.
- An alarm sent to the hospital’s security service and, if necessary, onwards to the relevant authorities and crisis management centres.
- Event logging: time, drone type, direction and trajectory. This record is the basis for reporting that surveillance may have been carried out near the tank.
- Continuous outdoor operation, in an enclosure with adequate ingress protection and with mains power and backup.
- A whitelist for the site’s own authorised drones, so that they do not trigger false alarms.
Detection and alarm instead of neutralisation
The system at a hospital detects and raises the alarm. Jamming a drone, taking control of it or destroying it requires separate authorisation and is the task of designated services. A passive device that only receives signals does not, as a rule, require a radio licence. It must, however, meet the requirements of the RED directive and have an EU declaration of conformity.
Limitations of RF detection
A passive RF system sees drones that transmit. It will not notice a drone flying autonomously along a pre-programmed route without a radio link, or one controlled via optical fibre. Drones that do not transmit in the bands typical for drones, including those connected through the LTE mobile network, may also escape it. Cover and masking protect against such drones, because they work regardless of how the drone is controlled.
How does an anti-drone net mask an oxygen tank?
An anti-drone cover is a lightweight, open supporting structure with a net stretched over and around the tank, including the vaporiser and fittings. The dispersing net stops a small drone or a dropped payload at a safe distance from the tank. The same net masks the tank.
Image recognition systems look for shapes and structures that match a pattern. Through its shape and printed graphics, the net changes the image of the tank seen from the air, so that it may stop resembling a gas or fuel tank. This makes it harder to recognise the object and to guide a drone precisely, including on the basis of satellite images.
A camouflage pattern cannot be carried over from one hospital to another. For each tank the surroundings, meaning the buildings, terrain and surfaces around it, must be analysed and the camouflage prepared individually. The masking material is subject to the same requirements as the net: it must be at least flame-retardant, weather-resistant and must not restrict ventilation of the vaporiser.
Anti-drone net parameters
- mesh no larger than 50 × 50 mm, which stops typical small drones and FPV drones,
- high-strength material: steel rope or synthetic fibre with high breaking strength,
- resistance to UV radiation and to temperatures from about −30°C to +60°C,
- material that is at least flame-retardant, because the net works in the vicinity of an oxygen tank,
- a tensioning and fastening system that allows a single segment to be replaced without dismantling the whole,
- an operating stock of net and fastening elements, for example 10% of the cover area.
What must a tank cover not obstruct?
A liquid oxygen tank is a process installation, and GMWP sets clear limits for a protective structure. The cover must not restrict ventilation, service access, evacuation, the operation of safety valves, tanker unloading, fire brigade intervention or the required safety distances. Nor may it obstruct the discharge of gas from vents and safety valves or create a space in which oxygen could accumulate.
The cover design must also take into account:
- air flow through the ambient vaporiser, so that the cover does not restrict vaporisation or cause excessive icing,
- snow, wind and ice loads in the structural calculations,
- oxygen-compatible materials in the zone directly next to the tank.
The fence around the tank area is made of non-combustible materials. According to GMWP, wood and other flammable materials are not used in it.
The tank often belongs to the oxygen supplier rather than the hospital. The solution must therefore be agreed from the outset with the tank owner and the liquid oxygen supplier, preferably in writing, and the works carried out so as not to interrupt oxygen deliveries and supply.
The net works outdoors all year round. The cover is inspected at least once a year and after every event: a storm, icing or a drone impact. Damaged segments are replaced from the stock, without dismantling the whole structure.
What happens to the oxygen supply when the tank is damaged?
Cover and masking reduce the risk of a hit, and detection gives security time to react, but none of them rules out an attack. If one happens, the installation must switch to another oxygen source. The PN-EN ISO 7396-1 standard and the GMWP guide describe a system of three sources: primary, secondary and reserve. When the tank is the primary source, the secondary source takes over the supply first and switches over automatically. The reserve source is permanently connected to the installation and maintains the supply when both of the others are unavailable.
The standard allows the reserve source to be started manually or automatically, depending on the type of source. Where there is a threat of attack, we recommend that the reserve also take over the supply automatically, because when the tank is damaged no one will have time to react manually. The switchover should trigger an alarm, and monitoring of the cylinder sources shows how long the oxygen will last.
Cylinder sources only make sense if they survive the same event. Cylinders or cylinder bundles, for both the secondary and the reserve source, should stand at a safe distance from the tank, so that damage to it, a fire or a leak does not destroy the structure in which they stand. A cylinder manifold placed right next to the tank, under the same shelter or behind the same wall, may be put out of action together with it.
The autonomy of cylinder sources is calculated in hours at the assumed consumption. A 50 l cylinder filled to 200 bar contains roughly 10 m³ of oxygen, which is why in a large hospital they are built from cylinder banks or bundles connected to manifolds. The principle of three sources is described in detail in the article A full oxygen tank is not yet continuity of supply.
What formalities apply to a tank cover?
A cover structure over the tank is a construction object. Depending on its size and foundation, it may require notification or a building permit under the Construction Law. This is best established at the design stage, not during installation.
Acceptance documentation should include at least:
- drawings and structural calculations,
- material data sheets and fire classifications of the net and the masking layer,
- agreements with the tank owner and the oxygen supplier,
- documentation of the RF detection system with the EU declaration of conformity,
- test and acceptance reports, including a test of switchover to the reserve source.
How does Medpipe help protect oxygen sources?
Medpipe designs and builds medical gas installations and supplies and services medical gas sources as a distributor and authorised service provider. We know liquid oxygen tanks from the technical side: how the vaporiser works, where the tanker has to drive up and what must not be covered.
We can prepare protection of the tank as one coherent solution: drone detection, a net with camouflage matched to the surroundings and cylinder sources with automatic switchover, agreed with the oxygen supplier and integrated with the existing medical gas monitoring system.
In chapter 7.2, GMWP points to a lightweight, open protective structure that limits the tank’s visibility and hinders the direct action of small unmanned aerial vehicles as a safeguard to consider in justified cases, especially in large hospitals, hub hospitals, facilities of strategic importance and facilities included in crisis response plans. The same chapter sets out the principles for configuring primary, secondary and reserve sources.
Frequently asked questions
Is an anti-drone net enough to protect an oxygen tank?
No. The net stops a drone and masks the tank, but it does not warn security and will not keep the supply going after the tank is damaged. Drone detection and cylinder sources with automatic switchover are also needed.
Why detect drones if the hospital cannot neutralise them?
A flight over the oxygen tank may be surveillance. The system records the event and alerts security and the relevant authorities, whether the filming is done by an amateur or a foreign intelligence service.
Does a passive drone detection system require a radio licence?
A device that only receives signals and transmits nothing does not, as a rule, require a radio licence. It must, however, have the EU declaration of conformity required by the RED directive. Radars and transmitting devices are subject to different rules.
What range should a drone detection system at a tank have?
It depends on the site and on how much time security needs to react. For a single hospital tank a few hundred metres is usually enough, and public tenders sometimes require at least 500 m.
Can a hospital jam or neutralise drones itself?
No. Neutralising drones, including jamming, requires separate authorisation and is the task of designated services. The system at the hospital detects and raises the alarm.
Where should the oxygen cylinder reserve be located?
At a safe distance from the tank, so that damage to it does not destroy the structure in which the cylinders stand. This applies to both the secondary and the reserve source. Both are permanently connected to the installation and, where there is a threat of attack, should take over the supply automatically.
Does a tank cover require a building permit?
It may require notification or a permit, depending on the size of the structure and its foundation. This must be established at the design stage.
Basis
- Medical Gases in Practice, Booklet 1, 2026 edition, INMED S.A.: chapter 7.2, location and protection of the liquid oxygen tank area, protective structure, primary, secondary and reserve sources
- PN-EN ISO 7396-1:2016-07: supply system with primary, secondary and reserve sources, switching between sources
- Directive 2014/53/EU (RED): requirements for radio equipment and the EU declaration of conformity
- Polish Construction Law Act of 7 July 1994: notification and building permit
If you are planning a modernisation or verifying an existing arrangement of supply sources, order the GMWP guide and check your installation against the criteria described in it.
See also: loss of continuity of oxygen supply, backup ward converted to ICU.
Prepared by: technical team of Małgorzata Dopierała, Damian Czyczyro and Przemysław Kostera — Medpipe Sp. z o.o., design, audits and inspections of medical gas installations. The article draws on the guide “Medical gases in practice. Volume 1” (GMWP), INMED S.A., chapter 7.2.